Hogar

>

Blog

>

Filtro de aire G4, F7 y F9: ¿Cuáles son las diferencias y cómo elegir??

Filtro de aire G4, F7 y F9: ¿Cuáles son las diferencias y cómo elegir??

Tabla de contenido

Comparación de filtros de aire G4, F7 y F9 por clase, tamaño de partícula, eficiencia y aplicación

Customer Problem

Overseas procurement managers and HVAC engineers frequently face confusion when reading technical submittals: “Why does one spec sheet say G4, while another lists ISO Coarse 75%? Can an F7 filter replace an F9 filter to save costs?” Misinterpreting filter rating standards leads to buying under-spec filters that fail audits, or over-spec filters that choke supply fans.

Cause & Principle

Air filter ratings define a filter’s ability to capture particles of specific micron sizes under defined airflows. Different filtration media, ranging from coarse synthetic fibers to ultra-fine meltblown polypropylene and glass fiber web structures, yield vastly different arrestance mechanics.

The industry is bridging two major standards:

  • En779 (Legacy European Standard): Classifies filters as Coarse (G1–G4), Medio (M5-M6), and Fine (F7–F9) based on average efficiency for 0.4 μm particles.
  • ISO 16890 (Current Global Standard): Measures efficiency across particle size fractions: ePM1 (0.3–1.0 μm), ePM2.5 (0.3–2.5 μm), and ePM10 (0.3–10 µm).
ISO 16890 particle size distribution and filter efficiency curve

Comparison Analysis

Característica G4 Air Filter F7 Air Filter F9 Air Filter
En779 / Clase ISOG4 / ISO Coarse 60–90%F7 / ePM1 50–65% (ePM2.5 >70%)F9 / ePM1 80–85%
Target PollutantsCoarse dust, polen, leaves, cabelloPolvo fino, PM2.5, bacteria carrier dropletsFine combustion particles, welding fumes
Typical StructurePleated panel, synthetic matPocket/Bag filter, rigid V-bankPocket/Bag filter, V-bank mini-pleat
Primary PlacementAHU air intake, primary protectionClimatización comercial, cleanroom pre-stageHigh-spec industrial, HEPA pre-stage
G4 panel, F7 pocket and F9 filter lineup with efficiency ratings

Cómo elegir

  • Choose G4 when: You need a low-cost, low-resistance barrier at the fresh air intake to protect fan motors and cooling coils, as with a G4 panel filter.
  • Choose F7 when: You are designing general HVAC systems for commercial spaces, public buildings, or standard manufacturing plants to meet health and comfort IAQ standards. An F7 pocket filter is a common choice.
  • Choose F9 when: You are supplying critical environments (p.ej. turbine intakes, pharmaceutical pre-filtration, automotive spray booths) where maximum particle interception before HEPA is non-negotiable.

Common Mistakes

  • Assuming F9 Can Act as a HEPA Filter: F9 captures fine particles well, but it does not achieve the 99.97% eficiencia en 0.3 μm required for HEPA certification.
  • Neglecting Electrostatic Discharge Effects: Some low-quality F7 synthetic filters rely purely on static charge; once discharged in high humidity, their real-world efficiency drops drastically.
Common mistakes: F9 is not HEPA and electrostatic discharge loss

The Airy Solution

  • Airy F7/F9 Pocket Filters: Built with ultrasonic seamless welding technology to prevent edge leakage, coupled with mechanically stable, non-discharging micro-synthetic media.
  • Strict Standard Compliance: All Airy filter media are tested to verify exact compliance with EN779 and ISO 16890 test protocols, ensuring your submittals pass local engineering audits smoothly.
Airy pink pocket filter used as an F7 or F9 stage
Airy white pocket filter for fine dust capture
Airy filter media test report under EN779 and ISO 16890
TTRI air filter test report confirming the rated efficiency

Preguntas frecuentes

What is the equivalent ISO 16890 rating for an EN779 F7 pocket filter?

An EN779 F7 filter typically corresponds to ISO ePM1 55–65% or ISO ePM2.5 70–80%, depending on the media structure.

How many pockets (bags) should I select for an F7 filter?

More pockets increase total media surface area, which reduces resistance and extends dust-holding capacity. Airy offers 3, 5, 6, and 8-pocket configurations.

Request Data Sheets and a Sample Kit
Need technical data sheets or test reports for G4, F7, or F9 filters? Request a free sample kit and detailed spec sheet from Airy’s overseas sales team.
G4–F9 Non-Woven Pocket Filter →
Comparación de filtros de aire G4, F7 y F9 por clase, tamaño de partícula, eficiencia y aplicación

Silvia

Fundador & Industrial Filtration Strategist I founded Airy Filter in 2009, trayendo 14+ Años de experiencia en soluciones de filtración de aire industrial y salas limpias.. Me especializo en entregar sistemas de alto rendimiento para cabinas de pintura., fabricación, y ambientes controlados. Hemos apoyado a clientes líderes como BYD, Geeley, ISUZU, CRRC, Midea, y farmacéutica Baiyunshan, con proyectos que abarcan sistemas de metro, salas limpias, e infraestructura internacional, incluyendo plantas de energía y cadenas de suministro globales. Si está buscando un socio de filtración confiable con experiencia comprobada en proyectos, no dude en comunicarse con nosotros: mi equipo y yo estamos listos para satisfacer sus necesidades..

Ponerse en contacto

*Respetamos su confidencialidad y toda la información está protegida.

Blogs populares

It seems we can't find what you're looking for.

Whatsapp
×

Obtenga su cotización de filtro de aire personalizado hoy!

Si necesita filtración de grado industrial o soluciones de modernización rápida, Entregamos filtros de ingeniería de precisión para optimizar sus operaciones.

Contáctenos

*Respetamos su confidencialidad y toda la información está protegida..